list all products >>

 

 
 


National Electric Codes > Article 338 - Service Entrance Cable

Article 338 - Service-Entrance Cable
 

Types SE and USE

•338-1. Definition. Service-entrance cable is a single conductor or multiconductor assembly provided with or without an overall covering, primarily used for services, and is of the following types:

(a) Type SE. Type SE, having a flame-retardant, moisture-resistant covering.

(b) Type USE. Type USE, identified for underground use, having a moisture-resistant covering, but not required to have a flame-retardant covering.

Cabled, single-conductor, Type USE constructions recognized for underground use may have a bare copper conductor cabled with the assembly. Type USE single, parallel, or cabled conductor assemblies recognized for underground use may have a bare copper concentric conductor applied. These constructions do not require an outer overall covering.

(FPN): See Section 230-41, Exception, item b for directly buried, uninsulated service-entrance conductors.

(c) One Uninsulated Conductor. If Type SE or USE cable consists of two or more conductors, one shall be permitted to be uninsulated.

•338-2. Uses Permitted as Service-Entrance Conductors. Service-entrance cable used as service-entrance conductors shall be installed as required by Article 230.

Type USE used for service laterals shall be permitted to emerge aboveground outside at terminations in meter bases or other enclosures where protected in accordance with Section 300-5(d).

•338-3. Uses Permitted as Branch Circuits or Feeders.

(a) Grounded Conductor Insulated. Type SE service-entrance cables shall be permitted in interior wiring systems where all of the circuit conductors of the cable are of the rubber-covered or thermoplastic type.

(b) Grounded Conductor Not Insulated. Type SE service-entrance cables without individual insulation on the grounded circuit conductor shall not be used as a branch circuit or as a feeder within a building, except a cable that has a final nonmetallic outer covering and is supplied by alternating current at not over 150 volts to ground shall be permitted as a feeder to supply only other buildings on the same premises.

Type SE service-entrance cable shall be permitted for use where the fully insulated conductors are used for circuit wiring and the uninsulated conductor is used for equipment grounding purposes.

(c) Temperature Limitations. Type SE service-entrance cable used to supply appliances shall not be subject to conductor temperatures in excess of the temperature specified for the type of insulation involved.

•338-4. Interior Installation Methods. In addition to the provisions of this article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Parts A and B of Article 336 and shall comply with the applicable provisions of Article 300.

(FPN): See Section 310-10 for temperature limitation of conductors.

•338-5. Marking. Service-entrance cable shall be marked as required in Section 310-11. Cable with the neutral conductor smaller than the ungrounded conductors shall be so marked.

•338-6. Bends. Bends in cable shall be made, and other handlings shall be such, that the protective coverings of the cable will not be damaged, and the radius of the curve of the inner edge of any bend shall not be less than five times the diameter of the cable.

 

 
Home | About Us | Products | Technical Details | Contact Us
St. Petersburg, Florida